§ 229-5. Fire suppression system required for canopy.  


Latest version.
  • All canopy installations shall contain an approved fire suppression system. The system must be arranged and installed for both automatic and manual operation in accordance with NFPA 17, Section 6-4, and NFPA 71, where electric actuation is used. A continuous backup power source capable of operating the system for at least 24 hours is required. Manual actuation shall be either mechanical or electric. Automatic system operation shall be accomplished pneumatically, using Underwriters' Laboratories, Inc. listed heat-activated devices, or electric, using Underwriters' Laboratories listed thermostats.